Indoor Switch Gear
Indoor Switch Gear
Indoor Switch Gear
Indoor Switch Gear
OUTDOOR SWITCH GEAR
OUTDOOR SWITCH GEAR
LED LIGHTING PRODUCTS
LED LIGHTING PRODUCTS
DC SOLAR SYSTEMS
DC SOLAR SYSTEMS
DC/AC SOLAR SYSTEMS
DC/AC SOLAR SYSTEMS
HOME SOLAR SYSTEMS
HOME SOLAR SYSTEMS
SOLAR SYSTEM COMPONENTS
SOLAR SYSTEM COMPONENTS
DIESEL GENERATORS
DIESEL GENERATORS
PETROL GENERATORS
PETROL GENERATORS
GW4: Outdoor 3-phase AC HV Disconnecting switch
brief introduction
GW4-40.5, 72.5, 126(W) / 630, 1250, 1600, 2000 Distyle Fracture level Rotation Outdoor Three Phase AC High Voltage Disconnecting Switch (hereinafter called switch) is supplied to high voltage circuitry for throwover under no load condition, and is used as electric disconnect for overhaulted high voltage bus, breaker and such high voltage electric device and high voltage circutry with electricity.
GW4 Outdoor AC High Voltage Disconnecting Switch conforms to the following standards:
GB 1984-89 "AC High Voltage Disconnecting Switch and Etarthing Switch" IEC 129 (1984) "AC High Voltage Disconnecting Switch and Earthing Switch". IEC 694 (1980) "Shared Terms for High Voltage Switch Devices and Control Devices Standards".
Designed to Switch!
Main technical data and mechanical feature data
| |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Main technical data (table1)
| |||||||||||||||
No
| Rated Value | GW4-40.5
| GW4-72.5
| GW4-126 | |||||||||||
1. |
Rated voltage |
40.5 |
72.5 |
126 |
|||||||||||
2. |
Rated current |
630 |
1250 |
1600 |
2000 |
630 |
1250 |
1600 |
2000 |
630 |
1250 |
1600 |
2000 |
||
3. |
Disconnecting Knife |
Rated withstand current(peak value) |
50 |
80 |
100 |
100 |
50 |
80 |
100 |
100 |
50 |
80 |
100 |
100 |
|
Rated short-time withstand current(effective value)KA |
20 |
31.5 |
40 |
40 |
20 |
31.5 |
40 |
40 |
20 |
31.5 |
40 |
40 |
|||
duration of rated short circuit (s) |
4 |
||||||||||||||
4. |
shaped earthing knife |
rated withstgand current |
25 |
||||||||||||
rated short-time withstgand current(effective value)KA |
10 |
||||||||||||||
duration of rated short circuit(s) |
4 |
||||||||||||||
5. |
shaped earthing knife |
rated withstgand current |
100 |
||||||||||||
rated short-time withstand current(effective value)KA |
40 |
||||||||||||||
duration of rated short circuit(s) |
4 |
||||||||||||||
6. |
rated short-time power frequency withstand voltage (effective value) KV |
to earth |
95 |
160 |
230 |
||||||||||
Across the Isolating distance |
118 |
197 |
265 |
||||||||||||
7. |
rated lighting impulse withstand voltage (effective value) KV |
to earth |
185 |
350 |
550 |
||||||||||
across the isolating distance |
215 |
385 |
630 |
||||||||||||
8. |
rated terminal static mechanical load N |
level vertical |
750 |
750 |
750 |
750 |
1000 |
1000 |
|||||||
level horizontal |
500 |
500 |
500 |
500 |
750 |
750 |
|||||||||
vertical force |
500 |
750 |
500 |
750 |
1000 |
1000 |
|||||||||
9. |
switch generatrix conversion current (generatrix conversion voltage 100V)A |
504 |
1000 |
1280 |
1600 |
504 |
1000 |
1280 |
1600 |
504 |
1000 |
1280 |
1600 |
||
10. |
wireless electricity disturbing level |
no |
no |
not over 2000 uV |
|||||||||||
11. |
mechanical endurance |
3000 |
3000 |
3000 |
mechanical feature data (table2)
| |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
No
| rated value
| GW4-40.5
| GW4-72.5
| GW4-126
| |||||||||
1. |
fracture distance of disconnecting switch after switch off |
400 |
600 |
1000 |
|||||||||
2. |
to earth insulation distance of conductive part |
400 |
600 |
1000 |
|||||||||
3. |
main circuit resistence |
200 |
150 |
95 |
75 |
220 |
155 |
100 |
80 |
245 |
170 |
110 |
90 |
4. |
closing and opening simultaneity of 3 phase main knife |
5 |
8 |
12 |
|||||||||
5. |
opening and closing time combined electric motor(s) |
CJ6:3.75, CJ2-XC:3 +-1 |
|||||||||||
6. |
weight of single pole (kg) |
125 |
150 |
160 |
190 |
200 |
240 |
All rights Reserved to Rockwill Electric Company