Rockwill Inverter Platform

brief introduction

      Turnkey Fully-Integrated Multi-Megawatt Medium Voltage (MV) Solution.

    • Leveraging Rockwill industry leading PV inverter platform, the Rockwill platform is a turnkey utility-grade multi-megawatt platform, complete with factory integrated step-up transformers, ring main unit (RMU), and power conversion electronics.

      Easy Utility-Ready Installation.

    • Rockwill platform is a turnkey utility-ready building block for PV installations. Installation is as simple as placing the unit by crane and connecting both ends. Because Roockwill platform is factory integrated, customers save money on field integration labor. Rockwill platform is standard 40 foot container size which can be easily transported.

designed to switch!

Specifications

1.0 MW

1.5 MW

2.0MW

Input parameters

Input Voltage Range

650-850 VDC

515-850 VDC

650 - 850 VDC

Maximum Array Input Voltage

1000 VDC

1000 VDC

1000 VDC

maximum operating input current*

1744 ADC

3160 ADC (2*1580 ADC)

3488 ADC (2*1744 ADC)

PV Array Configuration

Negative/Positive

Negative/Positive

Negative/Positive

DC Input Combiner Options

Combiner Bus Bar Input

12

24 (2*12)

24 (2*12)

Number of Inputs and Fuses

12 * 250A

12 * 250A

24 * 250A

Transfomer

Integrated MV Transfomer

Customer Specified

Customer Specified

Customer Specified

Efficiency

Inverter Maximum**

98.7%

98.7%

98.7%

European - Eta ***

98.5%

98.5%

98.5%

Output Parameters

Nominal Power

1.0 MW

1.5 MW

2.0 MW

Nominal Output Voltage

400 VAC

320 VAC

400 VAC

Output Voltage Range

320 - 460 VAC

256 - 368 VAC

320 - 460 VAC

Maximum Output Current/Phase

1587 A

1488 A (per 750KW)

1587 A (per 1MW)

Standby Consumption (tare losses including control power and aux.)

150W

300W

300W

Nominal Output Frequency, 3-Phase

50/60 Hz

50/60 Hz

50/60 Hz

Maximum Harmonic Distortion

<3% THD

<3% THD

<3% THD

Power Factor, Full Load

> 99%

> 99%

> 99%

Dynamic Power Fcator Control

+/- 0.8

+/- 0.8

+/- 0.8

Power Curtailment

0-100%, 1% step

0-100%, 1% step

0-100%, 1% step

Environment

Operating Temp Range (Nominal Power)

-30 C~+55C

-30 C~+55C

-30 C~+55C

Storage Temp Range

-30 C~+70C

-30 C~+70C

-30 C~+70C

Cooling

Forced

Forced

Forced

Noise Level (Distance of 3m)

< 65 dB (A)

< 65 dB (A)

< 65 dB (A)

Relative Humidity (Non-Condensing)

15 ~ 95%

15 ~ 95%

15 ~ 95%

Elevation (Max***)

4,000 m

4,000 m

4,000 m

Enclosure

Dimensions (HxWxD)

2103*2795*945mm

2103*4585*945mm

2103*2795*945mm

Weight

12,500kg

15,500kg

15,500kg

Finish

RAL 7035

RAL 7035

RAL 7035

Hood and Base Trim Finish

RAL 5001

RAL 5001

RAL 5001

Protection Rating

NEMA 3R/IP54

NEMA 3R/IP54

NEMA 3R/IP54

Warranty and Services

Five Year Warranty

Standard

Extended Warranty (1 ~ 5yrs)

Optional

Preventive Maintenance Agreement

Optional

Communication Interface

Modbus RS485

Standard

Modbus TCP/IP

Optional

Regulations and Standards Conformity

CE marks, VDE mark, Low Voltage Directive 2006/95/CE, EN 62116, EN 62093, IEC62109-1, IEC62109-2

Standard

Adavanced Grid Support (Incl. LVRT/DBEW)Option

Option

RD 1699

Standard

ENEL Connection Guidelines

Standard

All rights Reserved to Rockwill Electric Company